How to Calculate Fault Current for a Main Switchboard (MSB) from a Utility Transformer

What is the main source of fault MVA in a utility transformer feeding a Main Switchboard (MSB)?

The fault MVA at the source given by the utility is 1000 MVA with a percentage impedance of 5%. Assume the source impedance is purely reactive.

What is the maximum demand of the Main Switchboard (MSB) supplied by the transformer?

The maximum demand of the MSB is 1400 A.

How can we calculate the fault current at the MSB based on the given data?

The fault current at the MSB can be approximately determined to be 45,454 A by considering the transformer rating, percentage impedance, and fault MVA.

The Fault Current Calculation Process

To calculate the fault current at the Main Switchboard (MSB) supplied by a 22kV/400V, 1000 KVA transformer from the utility, we need to consider various factors:

The fault MVA at the source is 1000 MVA with a percentage impedance of 5%, assuming the source impedance is purely reactive.

The maximum demand of the MSB is 1400 A.

The feeder cable from the transformer to the MSB is 20 m long and is placed in the basement with an ambient temperature of 35 °C.

The transformer feeder cable consists of two sets of single-core PVC, copper cable installed flat and touching on a horizontal cable tray.

The fault current at the MSB is approximately 45,454 A, considering the given transformer rating, percentage impedance, and fault MVA.

Calculation Formula

We can use the following formula to calculate the fault current at the MSB:

Fault current (A) = Fault MVA / Rated Voltage (kV) * 1000

By substituting the values into the formula, we get:

Fault current = 1000 MVA / 22 kV * 1000 = 45,454 A (rounded to the nearest whole number)

Importance of Fault Current Calculation

Understanding and calculating the fault current at the MSB is crucial for designing and protecting the electrical system. Engineers can use this information to select appropriate protective devices like circuit breakers to ensure system safety and reliability.

In conclusion, the fault current at the MSB is approximately 45,454 A, considering the transformer rating, percentage impedance, and fault MVA.